A water main bursts near Circular Quay. Pressure in the street pipe drops in seconds, and the water inside your building wants to run the wrong way. What stops cleaning chemicals, garden fertiliser or pump water from sliding back into the public supply?
For many Sydney properties, the answer is one small brass device with two check valves inside. We call it a double check valve assembly, and it only protects you if someone tests it every year.
In this guide, we at Backflow Testing Sydney explain what double check valve testing is, who needs it, how often it is due and whether a valve can sit in a pit. We also point to what Sydney Water says, so you can check every claim yourself.
What Is Double Check Valve Testing?
Double-check valve testing is a yearly test by an accredited plumber that proves both check valves in your assembly seal tightly. If they do, the device passes, and we lodge the result with Sydney Water. If one leaks, the device fails and needs repair.
According to Sydney Water’s backflow guide for businesses, an accredited backflow plumber must test medium- and high-hazard devices when they are installed and every year after that. A general plumber cannot sign it off. The tester needs backflow accreditation and a calibrated test kit.
You might hear it called valve testing, DCV testing or simply backflow testing. It is the same job.
What Is a Double Check Valve Assembly?
A double check valve assembly (DCVA) is a backflow device with two spring-loaded check valves in a row. Each valve works on its own. If grit jams one open, the second still holds the line.
Here is what sits inside the assembly:
- Two independent check valves that close when water tries to run backwards
- Two shutoff valves, one at each end
- Test cocks, which are small ports where we connect our gauges
- A metal body that sits on the pipe, usually above ground
A double-check valve is built for medium-hazard connections. It is not the same as the small dual check valve built into many home water metres. Sydney Water installs its 20 mm and 25 mm metres with an integral device for low-hazard sites, and that device has no test cocks.
Why Sydney Properties Need Double Check Valve Testing
Backflow happens when used water flows back into the mains. Sydney Water says it can carry chemicals, oil, bacteria, mud and debris. It is more likely when pressure drops in the main, such as during a main break, or when a pump on your site pushes harder than the street supply.
Springs and seals wear out. A check valve can fail without any warning sign, so testing is the only way to know it still works.
The rules put the load on property owners. Sydney Water says you must have the right device, keep it maintained and use an accredited plumber to test it. It audits a sample of installations too. If you ignore a notice, it can test the device and bill you, restrict your water or disconnect you.
We have completed more than 500 tests over 10 years. Our customers include property managers in Parramatta, restaurant owners in Surry Hills and facilities teams in Macquarie Park. The notice looks the same for all of them, and so does the deadline.
When Is a DCV Acceptable Instead of an RPZ?
A DCV is acceptable when an accredited plumber rates your site as medium hazard. AS/NZS 3500.1 describes medium hazard as something that could endanger health. High hazard has the potential to cause death, so those sites need an RPZ, a registered break tank or a registered air gap.
This table shows what Sydney Water expects at each level:
| Hazard rating | Device Sydney Water expects | Annual test |
| Low | Integral dual check valve in a 20 mm or 25 mm meter, or a nontestable device on larger meters | No |
| Medium | Testable double check valve (double check detector assembly on fire services) | Yes |
| High | Registered break tank, RPZ device or registered air gap | Yes, for testable devices |
Two warnings apply here. First, if you skip the hazard assessment, Sydney Water assumes your site is high hazard and expects an RPZ. Second, ratings change when site activities change. Add chemical storage or a booster pump, and your DCV may no longer be enough.
For a longer comparison, read our guide on RPZ valve vs double-check valve in Sydney.
How Often Is a DCV Tested?
Once when it is installed, then every 12 months. Sydney Water keeps a register of testable devices and sends you a reminder each year.
Your plumber must lodge the result within 2 days of the test, according to Sydney Water. We lodge within 24 hours, and we email you the confirmation for your records.
If the device fails, we explain what went wrong. A licensed contractor then repairs or replaces it, and the fix is reported to Sydney Water. Missing the deadline costs more than the test itself, so have a look at what happens if you don’t test your backflow device in Sydney.
How We Go About Testing a Double Check Valve Assembly
Testing a double check valve assembly is a short, methodical job. Here is how we run it:
- We check the device, its serial number and the hazard rating on your notice.
- We connect a calibrated test kit to the test cocks.
- We test each check valve on its own to see if it closes tightly.
- We compare the readings with the pass criteria in AS/NZS 2845.3.
- We photograph the serial number and our test kit. Sydney Water can ask for these photos during an audit.
- We lodge the report through Sydney Water’s system and send you the confirmation.
If you have several devices on one site, we test them all in the same visit.
Can a DCV Be Installed in a Pit?
Usually, a pit is the wrong home for a testable DCV. Standards do not allow devices to be buried, and a pit that floods or fills with silt can undo the protection.
Western Australia’s Building and Energy guidance notes that AS/NZS 3500.1:2021 does not allow backflow devices to be buried. Only nontestable dual check valves may sit in a box below the surrounding surface. Sydney Water also points installers to AS/NZS 3500.1 and the manufacturer’s instructions.
Pits cause real trouble for testable valves:
- Standing water can reach the test cocks and open ports
- Tight space makes it hard to fit gauges and hoses.
- Silt and debris can foul the check valves.
- A confined pit adds risk for the person testing.
A better option is an above-ground assembly near the property boundary with clear access. Add a lockable cage if tampering is a worry.
Some older sites still have valves in pits. Rules can differ from site to site, so we inspect each one and tell you plainly whether it needs to move. You can also check an installer’s status on the Sydney Water backflow plumber search.
Double Check Valve Testing Near You
We offer double-check valve testing Sydney-wide, with next-day testing available. Our team covers the CBD around Circular Quay and Darling Harbour, Parramatta, Chatswood, North Sydney, Surry Hills, Newtown, Bondi, Macquarie Park, Liverpool, Penrith and Sutherland.
We charge a flat $199+GST per valve with no call-out fee. The price is the same for DCV, RPZ, pressure vacuum breaker and detector assemblies. If you are searching for valve testing near you, book your test here, and we will confirm a time.
Book Your Double Check Valve Test With Backflow Testing Sydney
If a Sydney Water notice is sitting on your desk, you have a clear next step. Our licensed team tests your valve, lodges the result within 24 hours and sends you the paperwork. It takes about two minutes to book online.
Book your test online or call us on 1300 911 124 and tell us what you have on site. If you are unsure whether you need a DCV or an RPZ, ask us and we will point you in the right way.
Frequently Asked Questions
How much does double check valve testing cost in Sydney?
At Backflow Testing Sydney, we charge a flat $199+GST per valve, with no call-out fee. That includes the on-site test, the report and Sydney Water lodgement within 24 hours. Ask us about pricing for several valves.
Who can test a double check valve in Sydney?
Only a licensed plumber with backflow accreditation can test it. Sydney Water requires this for medium- and high-hazard devices. Check that your tester holds the accreditation and lodges the report through Sydney Water’s system straight after the test.
What happens if my double check valve fails the test?
We tell you what failed and what to do next. A licensed plumber then repairs or replaces the valve, and the device is tested again. We refer repairs to a suitable contractor, so you are not left guessing.
What if I ignore a Sydney Water backflow notice?
Sydney Water can test the device and charge you, restrict your water supply or disconnect you. Fixing it later costs more than a routine test, so book as soon as the notice arrives.
Does a Sydney home with a normal water metre need a DCV?
Most standard homes do not. Sydney Water fits 20 mm and 25 mm metres with a built-in dual check valve for low-hazard sites. A testable DCV applies to medium hazard sites, which an accredited plumber confirms.